Web Reference: Apr 20, 2020 Β· According to section 517.19 (C) (1) operating room (wet procedure location according to NFPA 99) receptacles shall be connected to at least two branch circuits (normal-critical or critical-critical) and then section 517.20 (A) says that these spaces shall be protected by Isolated Power System or GFCI receptacles. GFCI devices should never be connected to an Isolated Power System. GFCIs will not operate properly and can result in unwanted ground connection in the Isolated Power System. Solution: Do an inspection of areas where isolated power is installed and if any GFCI are found on isolated power, replace with hospital grade duplex receptacles.